beautypg.com

Standard connection diagram, 1 standard connection diagram – Yaskawa iQpump Micro User Manual

Page 60

background image

3.1 Standard Connection Diagram

Connect the drive and peripheral devices as shown in

Figure 3.1

. It is possible to run the drive via the digital operator without

connecting digital I/O wiring. This section does not discuss drive operation;

Refer to Start-Up Programming & Operation

on page 83

for instructions on operating the drive.

NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate branch circuit short circuit protection

per applicable codes. The drive is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical amperes, 240 Vac

maximum (200 V Class) and 480 Vac maximum (400 V Class).

NOTICE: When the wiring distance is greater than 100 meters, pay special attention to the motor insulation voltage or use a drive duty

motor. Failure to comply could lead to motor insulation breakdown.

NOTICE: Correctly set Sink/Source jumper S3 for internal power supply. Failure to comply may result in damage to the drive.

Refer to I/O

Connections on page 79

for details.

NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.

NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less than 10 mA (reference value),

connect it to a photocoupler output (P1, P2, PC). Improper application of peripheral devices could result in damage to the photocoupler

output of the drive.

3.1 Standard Connection Diagram

60

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

This manual is related to the following products: