C3: Slip Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C3-01

(020F) Slip Compensation Gain Slip Comp

Sets the gain for the motor slip compensation function used for

motor 1.

Default: 0.0

Min.: 0.0

Max.: 2.5

C3-02

(0210)

Slip Compensation

Primary Delay Time

Slip Comp Time

Adjusts the slip compensation function delay time used for

motor 1.

Default: 2000 ms

Min.: 0

Max.: 10000

C3-03

(0211)

Slip Compensation

Limit

Slip Comp Limit

Sets an upper limit for the slip compensation function as a

percentage of motor rated slip for motor 1 (E2-02).

Default: 200%

Min.: 0

Max.: 250

C3-04

(0212)

Slip Compensation

Selection during

Regeneration

Slip Comp Regen

0: Disabled

1: Above 6 Hz

0: Disabled.

1: Enabled above 6 Hz

Default: 0

Range: 0, 1

u

C4: Torque Compensation

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C4-01

(0215)

Torque Compensation

Gain

Torq Comp Gain

Sets the gain for the automatic torque (voltage) boost function

and helps to produce better starting torque. Used for motor 1.

Default: 1.00

Min.: 0.00

Max.: 2.50

C4-02

(0216)

Torque Compensation

Primary Delay Time 1

Torq Comp Time

Sets the torque compensation filter time.

Default: 200 ms

Min.: 0

Max.: 60000

u

C6: Carrier Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C6-02

(0224)

Carrier Frequency

Selection

CarrierFreq Sel

1: 2.0 kHz

2: 5.0 kHz

3: 8.0 kHz

4: 10.0 kHz

5: 12.5 kHz

6: 15.0 kHz

7: Swing PWM1

8: Swing PWM2

9: Swing PWM3

A: Swing PWM4

B: LeakageRejection

F: Program

1: 2.0 kHz

2: 5.0 kHz (4.0 kHz)

3: 8.0 kHz (6.0 kHz)

4: 10.0 kHz (8.0 kHz)

5: 12.5 kHz (10.0 kHz)

6: 15.0 kHz (12.0 kHz)

7: Swing PWM1 (Audible sound 1)

8: Swing PWM2 (Audible sound 2)

9: Swing PWM3 (Audible sound 3)

A: Swing PWM4 (Audible sound 4)

B: Leakage Current Rejection PWM

C to E: No setting possible

F: User-defined (determined by C6-03 through C6-05)

Default: 7

Range: 1 to B; F

C6-03

(0225)

Carrier Frequency

Upper Limit

CarrierFreq Max

Determines the upper and lower limits for the carrier frequency.

Carrier Frequency

E1-04

Max Output

Frequency

Output Frequency

× (C6-05) × K

Output

Frequency

C6-03

C6-04

Default: 2.0 kHz

Min.: 1.0

Max.: 15.0

C6-04

(0226)

Carrier Frequency

Lower Limit

CarrierFreq Min

Default: 2.0 kHz

Min.: 1.0

Max.: 15.0

C6-05

(0227)

Carrier Frequency

Proportional Gain

CarrierFreq Gain

Default: 0

Min.: 0

Max.: 99

B.3 C: Tuning