n

P5-02: HAND Reference 1

Sets the frequency reference of HAND mode. When the drive is stopped, pressing the HAND key will start the drive and the

drive will accelerate to the P5-02 setting.

No.

Parameter Name

Setting Range

Default

P5-02

HAND Reference 1

0.0 to E1-04

40.0 Hz

n

P5-04: HAND Key Function Selection

Selects whether the HAND key on the HOA keypad is active. Disabling this function by setting P5-04 to 0 will prevent the

drive from entering HAND Mode.

No.

Parameter Name

Setting Range

Default

P5-04

HAND Key Function Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

n

Q1-01: PID Controller Setpoint 1

Sets the PID setpoint for the controller. The drive will use the system feedback signal and modulate the pump speed to regulate

the feedback at the Q1-01 setpoint. The units for Q1-01 are selected by b1-01 and the scaling is set in parameter P1-03. This

parameter is active when b1-01 (Reference Source) is set to 0 (HOA keypad).

No.

Parameter Name

Setting Range

Default

Q1-01

PID Controller Setpoint 1

0.0 to 6000.0

0.0 PSI

4.8 Detailed iQpump Parameter Descriptions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

161