Digital Operator Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1).
Cause
Possible Solutions
b5-01 is set to 1 or 2, enabling PID control, but the
lower limit for the frequency reference (d2-02) is
not set to 0 while reverse output is enabled
(b5-11 = 1).
Correct the parameter settings.
Digital Operator Display
Error Name
oPE10
V/f Data Setting Error
One of the following setting errors has occurred:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Cause
Possible Solutions
V/f pattern setting error.
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
Digital Operator Display
Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause
Possible Solutions
The following simultaneous contradictory settings
have occurred: C6-05 > 6 and C6-04 > C6-03
(carrier frequency lower limit is greater than the
upper limit).
If C6-05 ≤ 6, the drive operates at C6-03.
Correct the parameter settings.
The upper and lower limits between C6-02 and
C6-05 are contradictory.
Digital Operator Display
Error Name
oPE33
Net Incompatible
Parameter selection is incompatible with the selected network P9-99
Cause
Possible Solutions
When P1-01 = 3 (MEMOBUS Networking) and
P9-99 = 0 (A-Version 30034), one of the following
parameters has been set:
• P9-01 = 2 (Stop History)
• P9-05 = 3 (Follow Lead Speed)
Confirm parameter settings for P1-01, P9-01, P9-99, and P9-05.
5.4 Operator Programming Errors
194