Three-phase 400 v class drives – Yaskawa iQpump Micro User Manual
Page 220

u
Three-Phase 400 V Class Drives
Table A.4 Three-Phase 400 V Class Power Ratings
Item
Specification
Three-Phase Model
4V0002
4V0004
4V0005
4V0007
4V0009
Maximum Applicable Motor Capacity kW (HP)
<1>
0.75 (1.0)
1.5 (2)
2.2 (3)
3.0 (3)
3.7 (5)
Input
Input Current (A)
<2>
2.1
4.3
5.9
8.1
9.4
Output
Rated Output Capacity (kVA)
<3>
1.6
3.1
4.1
5.3
6.7
Output Current (A)
2.1
4.1
5.4
6.9
8.8
Overload Tolerance
120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: 380 to 480 V (proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power Supply
Rated Voltage
Rated Frequency
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V
<4>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Harmonic Corrective
Actions
DC Link Choke
Optional
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the
motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 460 V.
<4> DC is not available for UL standards.
Table A.5 Three-Phase 400 V Class Power Ratings Continued
Item
Specification
Three-Phase Model
4V0011
4V0018
4V0023
4V0031
4V0038
Maximum Applicable Motor Capacity kW (HP)
<1>
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
Input
Input Current (A)
<2>
14.0
20.0
24.0
38.0
44.0
Output
Rated Output Capacity (kVA)
<3>
8.5
13.3
17.5
23.6
29.0
Output Current (A)
11.1
17.5
23.0
31.0
38.0
Overload Tolerance
120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: 380 to 480 V (proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power Supply
Rated Voltage
Rated Frequency
Three-phase power: 380 to 480 V 50/60 Hz
DC power supply: 510 to 680 V
<4>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective
Actions
DC Link Choke
Optional
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should be equal to or greater than the
motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 460 V.
<4> DC is not available for UL standards.
A.1 Power Ratings
220