General Purpose Mode Application Preset

The purpose of this mode is to allow the drive controller to run a motor at a set speed without the PID process loop. This preset

is designed to simplify using the drive for applications other than pumping control. The default settings call for the frequency

reference to be an analog input and the run command to come from the terminal strip via a maintain contact closure. The PID

loop is disabled and no process feedback is required.

Required Control Wiring

No additional control wiring is required when the drive controller is at its default settings.

Start Up Procedure

1.

Set parameter A1-03 to 7770 (General Purpose Mode) to pre-set parameter values for this application.

2.

Set the source of the frequency reference for the drive controller in parameter b1-01. The default setting is from the

terminal strip via a 0 to 10 V analog signal wired into terminal A1.

3.

Set the source of the Run Command for the drive controller in parameter b1-02. The default setting is from the terminal

strip via a maintained contact closure.

4.

Set the Acceleration Time of the motor in parameter C1-01. This is the time to accelerate the motor from zero speed

to 60 Hz (E1-04, Maximum Output Frequency).

5.

Determine the stopping method of the motor. The default setting is coast to stop. To ramp the motor to a stop, set

b1-03 to 0 and then set the motor deceleration time in parameter C1-02. This is the time to stop the motor from to 60

Hz (E1-04, Maximum Output Frequency) to zero speed.

6.

Set the motor-rated current in parameter E2-01. This information can be found on the motor nameplate or specification

sheet.

7.

Set the number of motor poles in parameter E2-04 (2-pole motors have a rated RPM of slightly less than 3600 RPM;

4-pole motors have a rated RPM of slightly less than 1800 RPM). This information can be found on the motor

nameplate or specification sheet.

8.

Determine whether the drive controller should attempt to reset itself after a fault. The default setting is disabled. The

function is turned on by setting 1 to 10 reset attempts in parameter L5-01 and the time between each reset in parameter

L5-04.

9.

Set the minimum speed at which the motor can run in parameter P1-06. If the system has a minimum safe operation

speed, set it in P1-06. This will act as a lower limit of the frequency reference.

10.

The motor can be run in HAND (LOCAL) Mode for maintenance purposes by pressing the HAND key while the drive

is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Set P5-04 to 0 to disable

the HAND key. The default frequency reference is 0.0 Hz in HAND Mode. This can be changed in parameter P5-02.

The AUTO key has no effect with the default settings in the General Purpose Application Preset.

Related Parameters

No.

Parameter Name

Setting Values

A1-03

Initialize Parameters

Default: 0

Range: 0 to 5550; 6008, 6009, 7770, 7771

b1-01

Frequency Reference Selection 1

Default: 0

Range: 0 to 4

b1-02

Run Command Selection 1

Default: 0

Range: 0 to 3

b1-03

Stopping Method Selection

Default: 1

Range: 0 to 3

C1-01

Acceleration Time 1

Default: 20.0 s

Min.: 0.0

Max.: 6000.0

C1-02

Deceleration Time 1

Default: 10.0 s

Min.: 0.0

Max.: 6000.0

E1-04

Maximum Output Frequency

Default: 60.0 Hz

Min.: 40.0

Max.: 400.0

E2-01

Motor Rated Current

Default: Depends on o2-04

Min.: 10% of drive rated current

Max.: 200% of drive rated current

E2-04

Number of Motor Poles

Default: 2

Min.: 2

Max.: 48

4.7 iQpump Presets and Functions

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

107

4

Start-Up Programming & Operation