A.1 Power Ratings
u
Single-Phase 200 V Class Drives
Table A.1 Single-Phase 200 V Class Power Ratings
Item
Specification
Single-Phase Drive Model
<1>
BV0006
BV0010
BV0012
BV0018
Maximum Motor Size Allowed kW (HP)
<2>
1.1 (1)
2.2 (3)
3.0 (3)
3.7 (5)
Input
Input Current (A)
<3>
13.8
20.2
24.0
35.0
Output
Rated Output Capacity (kVA)
<4>
2.3
3.7
4.6
6.7
Output Current (A)
6.0
9.6
12.0
17.5
Overload Tolerance
120% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Single-phase power: 200 to 240 V
(both proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power Supply
Rated Voltage
Rated Frequency
Single-phase power: 200 to 240 V 50/60 Hz
DC power supply: 270 to 340 V
<5>
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective
Actions
DC Link Choke
Optional
<1> Drives with single-phase power supply input will output three-phase power and cannot run a single-phase motor.
<2> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 230 V.
<5> DC is not available for UL standards.