T: motor tuning, T1: induction motor auto-tuning, B.14 t: motor tuning – Yaskawa iQpump Micro User Manual
Page 277

B.14 T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
u
T1: Induction Motor Auto-Tuning
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
T1-01
(0701)
Auto-Tuning Mode
Selection
Tuning Mode Sel
2: Term Resistance
2: Stationary Auto-Tuning for Line-to-Line Resistance
Default: 2
Range: 2
–
T1-02
(0702)
Motor Rated Power
Mtr Rated Power
Sets the motor rated power as specified on the motor nameplate.
Note:
Use the following formula to convert horsepower
into kilowatts:
1HP = 0.746 kW.
Default:
<1>
Min.: 0.03 kW
Max.: 650.00
kW
–
T1-04
(0704)
Motor Rated Current
Rated Current
Sets the motor rated current as specified on the motor
nameplate.
Default:
<1>
Min.: 10% of
drive rated
current
Max.: 200% of
drive rated
current
–
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
B.14 T: Motor Tuning
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
277
B
Parameter List