beautypg.com

Yaskawa iQpump Micro User Manual

Page 106

background image

(P2-02) lower than the PID setpoint and set the Draw Down Level (P1-04) slightly above the PID setpoint to prevent

the drive from waking up until the water exceeds the desired depth setting. Sleeping helps the drive save energy and

mechanical wear. When P1-04 is set to 0 (default), the sleep function is disabled.

Related Parameters

No.

Parameter Name

Setting Values

A1-01

Access Level Selection

Default: 2

Range: 0 to 3

A1-03

Initialize Parameters

Default: 0

Range: 0 to 5550; 6008, 6009, 7770, 7771

E2-01

Motor Rated Current

Default: Depends on o2-04

Min.: 10% of drive rated current

Max.: 200% of drive rated current

E2-04

Number of Motor Poles

Default: 2

Min.: 2

Max.: 48

P1-03

Feedback Device Scaling

Default: 145.0 PSI

Min.: 0.1

Max.: 6000.0

P1-11

High Feedback Level

Default: 155.0 PSI

Min.: 0.0

Max.: 6000.0

P1-06

Minimum Pump Speed

Default: 40.0 Hz

Min.: 0.0

Max.: [E1-04]

P1-04

Start / Draw Down Level

Default: 0.0 PSI

Min.: -999.9

Max.: 999.9

P2-02

Sleep Level

Default: 0.0 Hz

Min.: 0.0

Max.: 6000.0

P4-10

AUTO Mode Operator Run Power Down Storage

Default: 0

Range: 0, 1

P5-02

HAND Speed Reference 1

Default: 40.0 Hz

Min.: 0

Max.: [E1-04]

P5-04

HAND Key Function Selection

Default: 1

Range: 0, 1

Q1-01

PID Controller Setpoint 1

Default: 0.0

Min.: 0.0

Max.: 6000.0

U1-99

Anti-No-Flow Timer

No signal output available

4.7 iQpump Presets and Functions

106

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual

This manual is related to the following products: