Yaskawa iQpump Micro User Manual

Page 120

background image

Setting 3: Lock Parameters

Parameters that are normally visible in the advanced access level (A1-01 = 2) are still visible, but the only parameters that can

be changed are A1-01 and A1-04.
The Auto Tuning and Pump Quick Setup menus will not be displayed.

Figure 4.19 Help Message Example (Home Screen)

Notes on Parameter Access

• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2

parameters cannot be modified.

• If a digital input terminal programmed for “Program lockout” (H1-oo = 1B) is enabled, parameter values cannot be

modified, even if A1-01 is set to 1 or 2.

• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the

digital operator until an Enter command is issued to the drive from the serial communication.

n

A1-03: Initialize Parameters

Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the

setting for A1-03 automatically returns to 0.

No.

Parameter Name

Setting Range

Default

A1-03

Initialize Parameters

0, 1110, 2220, 3330, 5550,

6008, 6009, 7770, 7771

0

Setting 1110: User Initialize

Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to

“1: Set defaults”.

Note:

User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to

clear the user-defined default values.

Setting 2220: 2-Wire Initialization

Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.

Setting 3330: 3-Wire Initialization

Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse

respectively.

S1

SN

FWD Run/Stop

2-Wire Control

Stop switch
(NC contact)

Operation switch
(NO contact)

S1

S2

SN

Run command
(Run on momentary close)

Stop command
(Stop on momentary open)

Sequence input common

3-Wire Control

Figure 4.20 2 & 3-Wire Control Wiring Examples

4.8 Detailed iQpump Parameter Descriptions

120

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual