Single-phase 200 v class, Three-phase 200 v class – Yaskawa iQpump Micro User Manual
Page 293

n
Single-Phase 200 V Class
Table C.2 Wire Gauge and Torque Specifications
Drive
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening
Torque
N•m (lb.in.)
BV0006
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
BV0010
R/L1, S/L2, T/L3
10
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
BV0012
R/L1, S/L2, T/L3
10
14 to 10
M4
2.3 to 2.5
(20.4 to 22.1)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
BV0018
R/L1, S/L2, T/L3
8
12 to 8
M5
2.3 to 2.5
(20.4 to 22.1)
U/T1, V/T2, W/T3
10
12 to 8
⊖, ⊕1, ⊕2
–
12 to 8
B1, B2
–
12 to 8
8
12 to 8
2 to 2.5
(17.7 to 22.1)
n
Three-Phase 200 V Class
Table C.3 Wire Gauge and Torque Specifications
Drive
Model
Terminal
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening
Torque
N•m (lb.in.)
2V0006
R/L1, S/L2, T/L3
14
18 to 14
M3.5
0.8 to 1.0
(7.1 to 8.9)
U/T1, V/T2, W/T3
14
18 to 14
⊖, ⊕1, ⊕2
–
18 to 14
B1, B2
–
18 to 14
14
18 to 14
2V0010
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
2V0012
R/L1, S/L2, T/L3
12
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
14
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
2V0020
R/L1, S/L2, T/L3
10
14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
14 to 10
⊖, ⊕1, ⊕2
–
14 to 10
B1, B2
–
14 to 10
10
14 to 10
C.1 UL Standards
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
293
C
Standards Compliance