B.8 L: Protection Function

L parameters provide protection to the drive and motor.

u

L1: Motor Protection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L1-01

(0480)

Motor Overload

Protection Selection

Mtr OL Charact

0: OL1 Disabled

1: VT Motor

2: CT Motor

3: Vector Motor

6: 50Hz VT Motor

0: Disabled

1: General purpose motor (standard fan cooled)

2: Drive dedicated motor with a speed range of 1:10

3: Vector motor with a speed range of 1:100

6: General purpose motor (50 Hz)

The drive may not be able to provide protection when using

multiple motors, even if overload is enabled in L1-01. Set L1-01

to 0 and install separate thermal relays to each motor.

Default: 1

Range: 0 to 3; 6

L1-02

(0481)

Motor Overload

Protection Time

MOL Time Const

Sets the motor thermal overload protection (oL1) time.

Default: 1.0 min

Min.: 0.1

Max.: 5.0

L1-03

(0482)

Motor Overheat Alarm

Operation Selection

(PTC input)

Mtr OH Alarm Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

3: Alarm only

Sets operation when the motor temperature analog input (H3-02

or H3-10 = E) exceeds the oH3 alarm level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

3: Alarm only (“oH3” will flash)

Default: 3

Range: 0 to 3

L1-04

(0483)

Motor Overheat Fault

Operation Selection

(PTC input)

Mtr OH Fault Sel

0 : Ramp to Stop

1: Coast to Stop

2: Fast-Stop

Sets stopping method when the motor temperature analog input

(H3-02 or H3-10 = E) exceeds the oH4 fault level.

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the deceleration time in

C1-09)

Default: 1

Range: 0 to 2

L1-05

(0484)

Motor Temperature

Input Filter Time (PTC

input)

Mtr Temp Filter

Adjusts the filter for the motor temperature analog input (H3-02

or H3-10 = E).

Default: 0.20 s

Min.: 0.00

Max.: 10.00

L1-13

(046D)

Continuous

Electrothermal

Operation Selection

Mtr OL Mem Sel

0: Disabled

1: Enabled

2: Enabled(RTC)

0: Disabled

1: Enabled

2: Enabled (RTC)

Default: 1

Range: 0 to 2

L1-22

(046D) Leakage Current Filter

Time Constant 1

Leakage Filter 1

Sets the time constant for reducing the sensitivity level when

detecting leakage current. Set in seconds and used when

operating at constant speed.

Note:

This parameter is available only when C6-02 is

set to B. To display this parameter, first set

C6-02 = B.

Default: 20.0 s

Min.: 0.0

Max.: 60.0

L1-23

(046D) Leakage Current Filter

Time Constant 2

Leakage Filter 2

Sets the time constant for reducing the sensitivity level when

detecting leakage current. Set in seconds and used during

acceleration and deceleration operation.

Note:

This parameter is available only when C6-02 is

set to B. To display this parameter, first set

C6-02 = B.

Default: 1.0 s

Min.: 0.0

Max.: 60.0

B.8 L: Protection Function

254