Yaskawa iQpump Micro User Manual
Page 288

No.
Description
Unit
Default Settings
−
Model
−
2V0040
2V0056
2V0069
o2-04
Drive Model Selection
Hex
6B
6D
6E
E2-11
Motor rated power
kW
11.0
15.0
18.5
b3-06
Speed Search current 1
−
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search (Speed
Estimation Type)
–
0.5
0.5
0.5
C6-02
Carrier frequency
−
7
7
7
E2-01
Motor rated current
A
39.7
53
65.8
E2-02
Motor rated slip
Hz
1.7
1.6
1.67
E2-03
Motor no-load current
A
11.2
15.2
15.7
E2-05
Motor line-to-line resistance
Ω
0.230
0.138
0.101
E2-06
Motor leakage inductance
%
19.5
17.2
15.7
E2-10
Motor Iron Loss
W
245
272
505
L2-02
Momentary power loss ride-through time
s
1.0
2.0
2.0
L2-03
Momentary power loss Baseblock time
s
0.9
1.0
1.0
L2-04
Momentary power loss voltage recovery time
s
0.3
0.3
0.6
L2-05
Uv detection voltage
V dc
190
190
190
L3-24
Motor acceleration time
s
0.265
0.244
0.317
L8-02
Overheat alarm level
°C
121
120
120
L8-09
Ground fault selection
−
1
1
1
L8-38
Carrier frequency reduction selection
−
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
B.16 Defaults by Drive Model
288
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual