Status

Description

Open

Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.

Closed

Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

L4-01

L4-01

+

L4-02

L4-01 – L4-02

Frequency reference

Frequency reference

+

L4-02

Frequency reference – L4-02

–L4-01

–L4-01

+

L4-02

–L4-01 – L4-02

During

Forward

During Reverse

Output frequency

0 Hz

OFF

OFF

OFF

ON

ON

ON

ON

Output frequency

User Set
Speed Agree 1

Figure 4.46 User Set Speed Agree 1 Time Chart

Setting 4: Frequency Detection 1

The output opens when the output frequency rises above the detection level set in L4-01 plus the detection width set in L4-02.

The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.

Status

Description

Open

Output frequency or motor speed exceeded L4-01 + L4-02.

Closed

Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

L4-02

Frequency
detection 1

ON

OFF

L4-02

L4-01

L4-01

Output Frequency

or Motor Speed

Figure 4.47 Frequency Detection 1 Time Chart

Setting 5: Frequency Detection 2

The output closes when the output frequency is above the detection level set in L4-01. The terminal remains closed until the

output frequency or motor speed fall below L4-01 minus the setting of L4-02.

Status

Description

Open

Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.

Closed

Output frequency or motor speed exceeded L4-01.

Note:

Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.

4.8 Detailed iQpump Parameter Descriptions

142

YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual