2.15. CETIL ER3 MODULE

(see Figure 2-52)

For ER3 use the following:

Cetil ER3 comverter module P/N 819523425

Sub (relay card) P/N 819523427

Cetil ER3 module + Sub P/N 819223425

Figure 2-52. Cetil ER3 Module + Sub

Connect pump communication wires to the 8 port comverter see Figure 2-53.:

Figure 2-53. Comverter External Connector

The following pinout is required for the Cetil application.

8 7 6 5 4 3 2 1

G

(chassis
ground)

G

(chassis
ground)

-Z +Y G

(chassis
ground)

G

(chassis
ground)

- Z

+ Y

Channel 2

Channel 1

8 Port CommVerter Operation and Installation Manual