2.7.5. Wayne Pump Configuration Example

The following paragraph provides the pump configuration required for models

3/G7237D/GHJKM/ - P/N 887695-0154/053

. Unit version:

54 IGEM

Verify programming codes on the pump as follows:

1. Set F01.00 to “1” for Serial Communications
2. Set F05.00 for the A side address (1-98)
3. Set F06.00 for the B side address (1-98)
4. Set F20.00 to “4” for US Current Loop
5. Set F20.01 to “02” for 9600 baud rate
6. Set F27.00 to “8” for Serial Comm
7. Set F27.01 to “0” for Serial Comm
8. Set F28.00 to “8” for Serial Comm
9. Set F28.01 to “0” for Serial Comm

N

N

O

O

T

T

E

E

The F27 and F28 settings are dependant on whether
the unit was shipped with a Pulse Output board. If the
dispenser does not have pulse output, the above
settings should work. If it does have a pulse output
option and a pulse output template loaded, they may
need to be changed. For serial communication, they
should be set as noted above.

Make sure that the Current Jumper on Current Loop module (P/N MO9680B029) is set to 45 mA and
Voltage Jumper is set to 24 VDC.
Verify that the serial communication parameters are set to: Baud 9600, Parity Odd, 1 stop bit (refer to
paragraphs 2.3

TYPES OF FUEL PUMP AND THEIR COMMUNICATION METHOD

and 5.5

SERIAL PORTS SETUP PROCEDURES

).


The Current Loop connector on the Wayne Pump – US/UK J25 is found on the top right hand side.