Lan to rs485 application, Lan to rs-485 application, Figure 2-7. commverter – lan to rs-485 application – Gasboy FuelOmat system 8 Popt Commverter User Manual
Page 30

2.5.
LAN to RS-485 APPLICATION
The LAN to RS-485 application is required when connecting fuel pumps and other serial devices to
home base controller that uses TCP/IP communication. In this configuration, the RS-485 Two-Port
module (P/N 819223460) is installed within the CommVerter.
If several CommVerter units are to be connected to the FCC, a Hub must be added to the network in
order to support several connections.
Figure 2-7. CommVerter – LAN to RS-485 Application
The CommVerter diverts the LAN communication to the relevant RS-485/422 device. The relevant
module is addressed with its IP address, and a unique port is configured during the device setup.
Interfaces using this mode of communication and conversion include Wayne Dart, Midco, L&T,
Tatsuno, Aplab, and more.
The following table provides the configuration of the RS-485 piggy-back board (Commverter
module) per type of pump.
Commverter Module
Configuration
Aplab (485)
9600,8,N,1
Avery (485)
5700,8,E,1
Gilbarco (485)
9600,8,N,1
L & T (485)
9600,8,N,1
Midco (485)
19200,8,N,1
Nuovo Pignone (485)
2400,8,O,1
Tatsuno (485)
19200,8.E,1
Wayne Dart (485)
9600,8,O,1
8 Port CommVerter Operation and Installation Manual
26