Mechanical, Environmental, Protection – Gasboy FuelOmat system 8 Popt Commverter User Manual
Page 20: Mechanical 1.5.5. environmental 1.6. protection

4 to 10 VDC (require wiring changes)
4
Pulsar Input High level sink
current (@15V)
3mA
5
Maximum pulse rate of
MPI-C at 50% duty cycle
Up to 5 KHz
6
In use "On" level (Input)
4 to 7 VDC
7
In use "Off" level (Input)
-1 to 1 VDC
8
In use Input impedance
10 KOhm
9
In use-max Input current
using external dry contact
(5VDC)
106 uA
10
In use-max Input current at 7
VDC
50 uA
11
12 VDC Output
25 mA max
1.5.4.
Mechanical
No.
Parameter
Value
1
Dimensions (HxWxD)
140 x 180 x 50 (mm)
1.5.5.
Environmental
No.
Parameter
Value
1 Operating
Temperature
-30
C to +55C
2
Operating Temperature (with power
supply)
-20
C to +50C
3
Storage Temperature
-30
C to +70C
1.6.
PROTECTION
The CommVerter in its 485 communication port (refer to Table 1-1) is protected electrically against
lightening and surges using transorbers and gas discharge (Arrosto) devices.
Additionally, grounding is required. Proper grounding is essential for protection to take place.
Refer to paragraph 4.4 - Grounding the Commverter.
8 Port CommVerter operation and installation manual