beautypg.com

Mechanical pump - pulser connections, Pulse rate, Interface connections – Gasboy FuelOmat system 8 Popt Commverter User Manual

Page 68: Figure 2-43. mpi-c j2 and j3 jumpers

background image

2.13.2.

Mechanical Pump - Pulser Connections

This paragraph describes the required wiring connections between the pulser in the mechanical
pump and the MPI-C. The system can accept many types of pulsers, please contact Gilbarco for
more information. Two types of pulsers can be found in pumps:

- Electronic pulser

- Mechanical pulser
Connect the MPI-C card to the Pulser in accordance to its characteristics.

2.13.2.1. Pulse Rate

The MPI-C may be configured to work with normal and high rate pulses (see Table 2-5), as may be
generated by Electronic Pulsers. The wiring is identical for both cases, yet the technician is required
to change jumper settings as detailed below. It is highly recommended to use normal rate pulsers to
prevent noise.

Table 2-5. Pulse Rate Specifications

Parameter

Normal Rate

High Rate

Minimum:7 VDC

Minimum: 4VDC

Input Voltage

Maximum: 15 VDC

Maximum: 12 VDC

Pulse Rate

Maximum: 0.5 KHz

Maximum: 5 KHz

Cycle Width

Minimum: 2 ms

Minimum: 0.2 ms

By default the MPI-C card is set to work with Normal Rate pulses: J2 and J3 jumpers' pins 1 and 2
are shorted (see Figure 2-44). In cases where the pump outputs high rate pulses, short pins 2 and 3.

Figure 2-44. MPI-C J2 and J3 Jumpers

2.13.2.2. Interface Connections

Figure 2-45 shows Mechanical Pump Interface Connections, including Mechanical and Electronic
Pulsers.

8 Port CommVerter Operation and Installation Manual

64