beautypg.com

5 power interface sensors, 6 reset cause sensor, 5 power interface sensors 7.4.6 reset cause sensor – Artesyn ATCA-8330 Installation and Use (April 2015) User Manual

Page 164: Table 7-3, Status sensor's sensor reading, Intelligent peripheral management controller

background image

Intelligent Peripheral Management Controller

ATCA-8330 Installation and Use (6806800S82B)

164

7.4.5

Power Interface Sensors

An Ericsson Power input module (PIM4000) is used for the 48v to 12v conversion monitoring.
The power input module includes sensors, which monitor the shelf's 48v input feeds current,
hold-up capacitor voltage, on-board temperature, and internal status. The status sensor
reading can be decoded as shown in

Table 7-3

.

7.4.6

Reset Cause Sensor

This sensor is implemented to monitor the last payload reset cause (hard reset, front panel
reset and so on). The IPMC evaluates the Reset Cause Register within the Glue Logic FPGA.

Table 7-3 Status Sensor's Sensor Reading

Bit 7

reserved

0

Bit 6

-48v Output Under
Voltage Alarm

0: Output Voltage is
below threshold
1: Output Voltage is
above threshold

Bit 5

Hot-swap Switch State

0: Hot-swap switch is off
1: Hot-swap switch is on

Bit 4

Holdup Switch State

0: Holdup Cap is not
connected to -48V Out
1: Holdup Cap is
connected to -48V Out

Bit 3

Reserved

0

Bit 2

Alarm Signal State

0: Feed loss alarm ceased
1: Feed loss alarm raised

Bit 1

Voltage Feed B Enabled

0: Enable B is Disabled
1: Enable B is Enabled

Bit 0

Voltage Feed A Enabled

0: Enable A is Disabled
1: Enable A is Enabled