7-4 Installing the DO-10 Digital Output
Module

The DO-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections

to the DO-10 module are presented in table 7.1. Specifications for the DO-10 module

are shown in table 7.2.

Table 7.1 DO-10 Digital Output Module Wiring Connections

Screw Terminal

Wiring Connection

1 and 2

Incoming network wiring, TP/FT-10 channel, polarity-
insensitive

3 and 4

Outgoing network wiring, TP/FT-10 channel, polarity-
insensitive

5

Unused

6 and 7

Incoming power wiring, 16-30VAC or VDC, 3.2 to 6.5VA
depending on load maximum, polarity-insensitive. If using DC
power, it is good practice to maintain continuity of the power
polarity throughout the network. Terminals 6 and 8 should be
the same polarity, and terminals 7 and 9 should be the same
polarity.

10

+ output of digital output 1

11

- output of digital output 1 (common to all outputs)

12

+ output of digital output 2

13

- output of digital output 2 (common to all outputs)

14

Unused

15

+ output of digital output 3

16

- output of digital output 3 (common to all outputs)

17

+ output of digital output 4

18

- output of digital output 4 (common to all outputs)

Table 7.2 LonPoint DO-10 Digital Output Module Specifications

Function

Description

Processor/memory

Neuron 3150 Chip, 10MHz, 56K flash memory

Service function

Recessed service switch, service LED, power/wink LED. Dual
tear-off bar-code Neuron ID self-adhesive tag for application to
red-line drawings in the field

I/O

4 digital outputs, 0-12V, 100mA source/sink maximum on any
one output, 110mA source/400mA sink combined; separate
status LEDs for each output; separate hand/off/auto front
panel DIP switches for each output

I/O isolation

100V, transformer isolation. Outputs are isolated from the input
power and the network but not from each other.

Transceiver type

FTT-10A with blocking capacitors for compatibility with link
power channel

Network connector

Phone plug connector accessible from front panel

Input power

16-30VAC or VDC @ 3.2 to 6.5VA depending on load,
internally isolated power supply

Mounting

Type 1 or Type 1D Base Plate

Temperature

-40 to +85°C, operating and non-operating

Humidity

10 to 95% RH @ 50°C