7-4 Installing the DO-10 Digital Output
Module
The DO-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections
to the DO-10 module are presented in table 7.1. Specifications for the DO-10 module
are shown in table 7.2.
Table 7.1 DO-10 Digital Output Module Wiring Connections
Screw Terminal
Wiring Connection
1 and 2
Incoming network wiring, TP/FT-10 channel, polarity-
insensitive
3 and 4
Outgoing network wiring, TP/FT-10 channel, polarity-
insensitive
5
Unused
6 and 7
Incoming power wiring, 16-30VAC or VDC, 3.2 to 6.5VA
depending on load maximum, polarity-insensitive. If using DC
power, it is good practice to maintain continuity of the power
polarity throughout the network. Terminals 6 and 8 should be
the same polarity, and terminals 7 and 9 should be the same
polarity.
10
+ output of digital output 1
11
- output of digital output 1 (common to all outputs)
12
+ output of digital output 2
13
- output of digital output 2 (common to all outputs)
14
Unused
15
+ output of digital output 3
16
- output of digital output 3 (common to all outputs)
17
+ output of digital output 4
18
- output of digital output 4 (common to all outputs)
Table 7.2 LonPoint DO-10 Digital Output Module Specifications
Function
Description
Processor/memory
Neuron 3150 Chip, 10MHz, 56K flash memory
Service function
Recessed service switch, service LED, power/wink LED. Dual
tear-off bar-code Neuron ID self-adhesive tag for application to
red-line drawings in the field
I/O
4 digital outputs, 0-12V, 100mA source/sink maximum on any
one output, 110mA source/400mA sink combined; separate
status LEDs for each output; separate hand/off/auto front
panel DIP switches for each output
I/O isolation
100V, transformer isolation. Outputs are isolated from the input
power and the network but not from each other.
Transceiver type
FTT-10A with blocking capacitors for compatibility with link
power channel
Network connector
Phone plug connector accessible from front panel
Input power
16-30VAC or VDC @ 3.2 to 6.5VA depending on load,
internally isolated power supply
Mounting
Type 1 or Type 1D Base Plate
Temperature
-40 to +85°C, operating and non-operating
Humidity