beautypg.com

Network cabling - tp/ft-10 channel – Echelon LonPoint Module User Manual

Page 24

background image

3-2

Network Cabling and Connections

Network Cabling - TP/FT-10 Channel

The LonPoint modules (excluding some LPR Routers) use Echelon’s FTT-10A Free

Topology Transceiver for network communications. This transceiver operates at 78

kilobits per second and is designed to support free topology wiring; it will accommodate

bus, star, loop, or any combination of these cabling topologies using a twisted pair cable.

By eliminating restrictions on the cabling topology, the installer is free to locate

LonPoint modules anywhere on the network cabling provided only that the maximum

cabling distance limitations are observed99 This capability simplifies system installation

and makes it easy to add nodes should the network need to be expanded. Figures 3.1

through 3.5 present five typical network topologies.

In free topology cabling it is necessary to use one Echelon Model 44100 terminator.

In bus topology cabling it is necessary to use two Echelon Model 44101 terminators.

Terminators are required for proper network operation and must not be omitted.

Termination

Figure 3.1 Singly Terminated Bus Topology (Model 44100 Terminator)

Termination

Figure 3.2 Star Topology (Model 44100 Terminator)

Termination

Figure 3.3 Loop Topology (Model 44100 Terminator)