Echelon LonPoint Module User Manual
Page 108
11-4
Installing the LPR Router
Modules
Table 11.1 LPR Router Wiring Connections
Screw Terminal
Wiring Connection
1 and 2
Incoming network wiring, polarity-insensitive - CHANNEL A
3 and 4
Outgoing network wiring, polarity-insensitive - CHANNEL A
5 and 14
Cable shields - terminals 5 and 14 are internally connected.
6 and 7
Incoming power wiring, 16-30VAC or VDC, 2.0VA, polarity-
insensitive. If using DC power, it is good practice to maintain
continuity of the power polarity throughout the network. Terminals 6
and 8 should be the same polarity, and terminals 7 and 9 should be
the same polarity.
10 and 12
Unused
Jumpered together internally - may be used to land extra wires
11 and 13
Unused
Jumpered together internally - may be used to land extra wires
15 and 16
Incoming network wiring, polarity-insensitive - CHANNEL B
17 and 18
Outgoing network wiring, polarity-insensitive - CHANNEL B
Table 11.2 LonPoint LPR Router Module Specifications
Function
Description
Processor
Two Neuron 3150 Chips, 10MHz
Service function
Recessed service switch, service LED. Dual tear-off bar-code Neuron
ID self-adhesive tag for application to red-line drawings in the field
Transceiver type
Varies by model
Network connector
Two phone plug connectors accessible from front panel - one per
channel
Input power
16-30VAC or VDC @ 2.0VA, internally isolated power supply
Mounting
Type 2 or Type 2D Base Plate
Temperature
-40 to +85°C, operating and non-operating
Humidity
10 to 95% RH @ 50°C
EMI
FCC A, CE Mark
Safety agency
UL 916