Echelon LonPoint Module User Manual
Page 33

LonPoint Hardware Guide
3-11
Tables 3.4 and 3.5 present the wire gauge that should be used in order to deliver the
specified power (total VA) across the distance shown. These tables only include wire
gauges from 24AWG (0.5mm) to 12AWG (2mm) as these are the wire gauges
supported by the Base Plate screw terminals. For the supply cabling use at least
24AWG/0.5mm, 90° C rated wire.
To determine the total power that a power cable must carry, total the VA
requirements for all of the devices that will be drawing power from that cable,
including both LonPoint modules and other devices. The VA ratings for the
LonPoint Modules are shown in the module data sheets and are summarized in the
following table.
Table 3.3 VA Ratings for LonPoint Modules
LonPoint Module
VA Rating
DI-10
2.2VA
DO-10
6.5VA
DIO-10
4.75VA
AI-10 (all modes except 2-wire mode)
2.1VA
AI-10 (2-wire mode)
4.5VA
AO-10
4.5VA
SCH-10
2.4VA
LPR
2.0VA
To determine what gauge cable (in AWG or metric) will be required based on the total distance of
the power cabling, refer to table 3.4 for cabling measured in AWG and table 3.4 for cabling
measured in mm. If the wire gauge used is smaller than required, improper operation of one of
more modules will result. All data in tables 3.4 and 3.5 assume an average wire temperature of
+55°C.
Table 3.4 Power Cabling Requirements in AWG
Load (VA)
Feet
Meters
10
15
20
25
30
40
55
75
100
130
180
200
35
10.7
22
22
22
22
22
22
22
22
22
22
22
22
40
12.2
22
22
22
22
22
22
22
22
22
22
22
20
55
16.8
22
22
22
22
22
22
22
22
22
22
20
20
65
19.8
22
22
22
22
22
22
22
22
22
20
20
18
70
21.3
22
22
22
22
22
22
22
22
22
20
18
18
75
22.9
22
22
22
22
22
22
22
22
22
20
18
18
90
27.4
22
22
22
22
22
22
22
22
20
20
18
18
100
30.5
22
22
22
22
22
22
22
22
20
18
18
16
105
32.0
22
22
22
22
22
22
22
20
20
18
18
16
115
35.1
22
22
22
22
22
22
22
20
20
18
16
16
135
41.1
22
22
22
22
22
22
22
20
18
18
16
16
145
44.2
22
22
22
22
22
22
20
20
18
18
16
16
150
45.7
22
22
22
22
22
22
20
20
18
16
16
16
AWG