Chapter 10: OPERATION

Step 3. Reset the failure information.

There are 3 failure reset methods described below

3-1. Resetting the failure information using the FAULT RESET key

The reset operation mode differs depending on the DIP switch 4 setting (

p. 1-3

).

• One touch mode: When DIP switch 4 is set to "OFF" (default)

Press the FAULT RESET key.
The GENERAL indicator goes off, and the
SX-2000 system returns to normal state.

Goes off

• Accidental operation prevention mode: When DIP switch 4 is set to "ON"

Press the FAULT RESET key 3 times. Hold down the key for 2 seconds or more for the third time.
(Refer to the figure below.)
When 2 seconds elapse after holding down the key for the third time, the GENERAL indicator goes
off, and the SX-2000 system returns to normal state.

Goes off

1st time

2nd time

3rd time

FAULT RESET key

ON

OFF

0.1 – 2
seconds

0.1 – 2
seconds

Over 2 seconds

Failure reset execution

2 seconds

Within 2
seconds

Within 2
seconds

Note
When the FAULT RESET key remains unpressed for 2 seconds or more, the operation so far
performed becomes invalid.

3-2. Resetting the failure information by way of the Data input terminals (RES terminals)

According to the DIP switch 4 setting (

p. 1-3

), short the Data input terminals (RES terminals) at the

same timing as the FAULT RESET key is pressed.

• When DIP switch 4 is set to "OFF" (default) (one touch mode)

Over 0.1 seconds

Short

• When DIP switch 4 is set to "ON" (accidental operation prevention mode: )

0.1 – 2
seconds

Short

Short

Short

0.1 – 2
seconds

Over 2 seconds

Failure reset execution

2 seconds

Within 2
seconds

Within 2
seconds