Chapter 10: OPERATION

2. MAKING GENERAL URGENCY ALL-CALLS

If normal broadcasts cannot be made due to system failure or some trouble, only an all-call is possible in the
following procedure.
This is a broadcast made by bypassing the CPU*

1

that normally operates in the SX-2000 system. (For details,

see the separate Installation Manual, "Installation" and "Connections.")
If the SX-2000 system receives a 24 V emergency cutoff signal*

2

, the general urgency all-call is disabled

because the emergency broadcast system takes precedence over the SX-2000 system.

*

1

CPU is a central processing unit, which is built in the SX-2000SM, SX-2000AI, SX-2100AI, SX-2000AO, and
SX-2100AO.

*

2

In the SX-2000 system, a 24 V emergency cutoff input terminal that allows control of an emergency audio
input is provided on the SX-2000AO's rear panel. When the SX-2000 system is combined with another
emergency broadcast system, a 24 V DC is normally kept being supplied to this emergency cutoff input
terminal and is cut off (24 V emergency cutoff function) in emergency situations. This interrupts the general-
purpose broadcast from the SX-2000, allowing the emergency broadcast system to override it. (For details,
see the separate Installation Manual, "Installation.")

General urgency all-calls can be made following the procedure below independently of settings performed
using the SX-2000 Setting Software.

2.1. Making General Urgency All-Calls from the RM-200SA

Open the cover of the General Urgency All-Call key, then while holding down the key, wait about 4 seconds
until the Failure indicator lights red and begin to make microphone announcements.

Cover

General Urgency All-Call key

Lights red

Failure Indicator

1

2

3

4

5

6

Note
The RM-200SA's DIP switch 5 (factory default: ON)
must be preset to ON to enable the CPU OFF function
(general urgency all-call).