beautypg.com

Detecting fault, Fault detection setting example – Toa SX-2000 Series Manual User Manual

Page 124

background image

10-19

Chapter 10: OPERATION

7. DETECTING FAULT

If a malfunction occurs within the SX-2000 system, the fault state can be indicated, acknowledged or reset
using the following keys or control terminals.

• FAULT ACK and FAULT RESET keys on the SX-2000SM
• Data input terminals (ACK terminals and RES terminals) on the SX-2000SM
• Control input terminals of the SX-2000SM, SX-2100AI, SX-2000AO, SX-2100AO, and SX-2000CI
• Function keys on the RM-200SA or RM-200SF.

Note
Regarding the setting procedures for detecting fault within the SX-2000 system, refer to the separate software
instruction manual. (See the separate Setting Software Instructions, "Basic Settings.")

7.1. Fault Detection Setting Example

The method to detect the fault within the system using the SX-2000SM, RM-200SF, and RM-210 is described
below.

[System configuration]

SX-2000SM

VP-200VX

VP-200VX

BGM Player 1

BGM Player 2

Power amplifiers

VP-2064

SX-2100AO

SX-2100AI

1F

2F

GF

ZONE 1F

ZONE 2F

ZONE GF

SX-200RM

D-921E

VP-200VX

SW-HUB

RM-200SF

RM-210