System Event Log Troubleshooting Guide for Intel

®

S5500/S3420 series Server Boards

Cooling subsystem

Revision 1.0

Intel order number G74211-001

41

Table 43: Discrete Thermal Sensors

– Next Steps

Sensor

Number

Sensor Name

Event

Type

Event Trigger Offset

Description

Next Steps

Hex

Description

66h

P1 VRD Hot

05h

01h

Limit Exceeded

Processor1 voltage
regulator overheated

1. Check for clear and unobstructed airflow into and out of chassis.

2. Ensure SDR is programmed and correct chassis has been selected.

3. Ensure there are no fan failures.

4. Ensure the air used to cool the system is within the thermal

specifications for the system (typically below 35°C).

67h

P2 VRD Hot

Processor2 voltage
regulator overheated

6ah

IOH Thermal Trip

03h

01h

State Asserted

I/O Hub (IOH) overheated