Troubleshooting, Restoring factory default settings, Error codes – Banner SureCross DX80 Wireless Networks User Manual
Page 75: Data logger error codes
![background image](/manuals/587623/75/background.png)
I/O Point
Floating Point Register
1
1001, 1002
2
1003, 1004
3
1005, 1006
4
1007, 1008
5
1009, 1010
Troubleshooting
Restoring Factory Default Settings
Restoring the factory default settings resets the settings for:
• IP Address: 192.168.0.1
• Root Login: root
• Root Password: sxi
• HTTP Port: 80
• Modbus Server Port: 502
• Telnet Port: 23
• EtherNet/IP Protocol: Disabled
To restore these settings, leave the device powered up and run-
ning and follow these steps:
1. Open the DX80 Gateway Pro or DX83 Ethernet Bridge hous-
ing to access the board
2. Install the initialization (init) jumper on the pins shown
3. Wait 30 seconds
4. Remove the jumper
5. Cycle power to the device
Using the configuration web page, verify the parameters have re-
turned to the factory defaults listed.
Initialization Pins
Error Codes
The following are the error codes associated with the Web Configurator.
Data Logger Error Codes
The following Status messages may appear for an event or data log file.
OK . The system is operating normally.
Error: -n. A file system error has occurred. Refer to the file system error codes listed below.
SureCross Web Configurator
rev. -
www.bannerengineering.com - tel: 763-544-3164