Output Units
Units
Description
Definition
6
Signed Analog, 0 to
20 mA
For a signed value, such as temperature, that is to be converted to a mA out value. Use null to
set the start point and span to define the range. The null value is the starting temperature to be
associated with 0 mA. The span is the entire temperature range that is to be associated with 0 to
20 mA.
LCD: 0.00mA–20.00mA
7
Unsigned Analog, 0
to 20 mA
For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to
set the start point and span to define the range. The null value is the distance to be associated
with 0 mA. The span is the entire distance range that is to be associated with 0 to 20 mA.
LCD: 0.00mA–20.00mA
8
Signed Analog, 4 to
20 mA (A)
In older models, this units type is for degree Celsius conversions only. Use null to set the start
point and span to define the range. The null value is the starting temperature to be associated
with 4 mA. The span is the entire temperature range that is to be associated with 4 to 20 mA. For
newer firmware models, type codes 8 and 9 are treated the same.
LCD: 4.00mA–20.00mA
9
Signed Analog, 4 to
20 mA (B)
In older models, this units type is for degree Fahrenheit conversions only. Use null to set the start
point and span to define the range. The null value is the starting temperature to be associated
with 4 mA. The span is the entire temperature range that is to be associated with 4 to 20 mA. For
newer firmware models, type codes 8 and 9 are treated the same.
LCD: 4.00mA–20.00mA
10
Unsigned Analog, 0
to 10V
For an unsigned value, such as 0 to 20 mA, that is to be converted to a voltage out value. Use the
null to set the start point and span to define the range. The null value is the distance to be associ-
ated with 0V. The span is the entire distance range that is to be associated with 0 to 10V.
LCD: 0.00V–10.00V
11
Counter, 16-bit
The 16-bit counter value records counts up to 65535.
LCD: 0000
12
Unsigned Analog, 4
to 20 mA
For an unsigned value, such as 0 to 10V, that is to be converted to a mA out value. Use the null
to set the start point and span to define the range. The null value is the distance to be associated
with 4 mA. The span is the entire distance range that is to be associated with 4 to 20 mA.
LCD: 4.00mA–20.00mA
Battery Powered Sensor Options
Sensor Power Supply
Select a power supply for the sensor device. Select Supply 1 through 4 to indicate the external device is powered from one of the Node’s
supplied switch power connectors.
External. The sensor is powered from outside the Node.
Supply #1. Switched power 1 (SP1)
Supply #2. Switched power 2 (SP2)
Supply #3. Switched power 3 (SP3)
Supply #4. Switched power 4 (SP4)
SureCross Web Configurator