Remote i/o – Banner SureCross DX80 Wireless Networks User Manual
Page 19
![background image](/manuals/587623/19/background.png)
For example, thermocouple inputs are multiplied by 20 before being written to the Modbus register. To convert this register value back to
a temperature reading use the Scaling screen.
The Offset value can be used to account for errors introduced into the sensor system, such as errors introduced because of wiring
lengths in a thermocouple input system.
Other Commands
Prev and
Next
If there are more than 16 devices or rules/
maps, use the Prev and Next buttons to display
the next screen of information.
Up-
date
Clicking the Update button sends information to the
Ethernet Bridge or GatewayPro or retrieves infor-
mation depending on which checkboxes are selec-
ted: Change or Get/Send All. Updating information
does not save configuration information perma-
nently to the XML file.
Remote I/O
The Remote I/O configuration page defines up to 32 external communication registers when the DX80 Gateway is defined as a Modbus
RTU Master.
This table is used only when the Gateway is a Modbus RTU master and it is communicating with Modbus slave devices, typically DX85
Expanded Remote I/O devices.
SureCross Web Configurator
rev. -
www.bannerengineering.com - tel: 763-544-3164
19