23
SPEED
RAMP
OUTPUT
(P.199)
Value of the speed reference signal immediately after the
speed loop
S
-
CURVE
block
24
TAPER
PERCENT
(P.859)
Percent reduction to be applied to the tension reference
from the taper function
25
TEN
LOOP
ERROR
(P.834)
Tension/current loop error signal after scaling
26
TEN
PI
KP
OUT
(P.879)
Value of the tension loop pi proportional gain
27
TEN
RAMP
OUTPUT
(P.842)
Output of the tension major loop ramp block after
tension-to-current conversion
28
TEN
TO
CURRENT
OUT
(P.876)
Output of the tension loop’s tension-to-current scaling
block
29
TRIM
OUTPUT
(P.197)
Actual signal used to trim the selected speed loop
reference signal
30
UNWIND
DIAMETER
IN
(P.828)
Analog input signal (TB 16, 17) when
DIAMTER
/
TAPER
SELECT
(P.870) =
DIAMETER
31
Indirect Register Status
Bit-packed word containing information on
0 to 6
Offending register number.
0 = No error
7 to 12
Reserved
13
Error - Not found
14
Error - Output parameter
15
Network sync
Table 7.12 – WebPak 3000 Register Map, Drop_3: Master Write Registers, FULL Connection. Tunable/Configurable Data (Drive Input Data)
Register
Bit
Parameter Name (Number)
Description
Settings
32
AutoMax Indirect Register 1
Value to be written to the parameter selected in the
corresponding Drop 2 register
33
AutoMax Indirect Register 2
Value to be written to the parameter selected in the
corresponding Drop 2 register
34
AutoMax Indirect Register 3
Value to be written to the parameter selected in the
corresponding Drop 2 register
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.
Table 7.11 – WebPak 3000 Register Map, Drop_3: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data) (Continued)
Register
Bit
Parameter Name (Number)
Description
Settings
Runtime signal data are updated by the regulator every 10 msec.