Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual
Page 46

5-
16
Aut
o
Max
Net
w
or
k Comm
unicat
ion
O
p
tion
B
oard
Table 5.17 – FlexPak 3000 Drop_4: Master Write Registers, FULL Connection. Tunable Data (Drive Input Data)
Register
Bit
Parameter Name (Number)
Description
Settings
32
ANLG
IN
1
ZERO
ADJ
(P.414)
I/O Expansion kit analog input 1 zero adjust
33
ANLG
IN
1
GAIN
ADJ
(P.415)
I/O Expansion kit analog input 1 gain adjust
gain * 1000
34
ANLG
IN
2
ZERO
ADJ
(P.416)
I/O Expansion kit analog input 2 zero adjust
35
ANLG
IN
2
GAIN
ADJ
(P.417)
I/O Expansion kit
ANALOG
INPUT
2
GAIN
ADJUST
gain * 1000
36
LEVEL
DETECT
1
THRESH
(P.603)
Level detector 1 threshold
% * 10
37
LEVEL
DETECT
1
DELAY
(P.604)
Level detector 1 delay time
seconds * 10
38
LEVEL
DETECT
2
THRESH
(P.606)
Level detector 2 threshold
% * 10
39
LEVEL
DETECT
2
DELAY
(P.607)
Level detector 2 delay time
seconds * 10
40
PLL
MAXIMUM
ERROR
(P.308)
Max. allowed change in line period per AC line cycle
µsec
41
ENHANCED
FLD
VOLT
ADJ
(P.500)
Adjusts the field output voltage
42
FIELD
ECONOMY
DELAY
(P.501)
Time between stopping and entering field economy
minutes
43
OPEN
SCR
SENSITIVITY
(P.600)
Open
SCR
detection sensitivity adjustment
44
OPEN
SCR
TRIP
THRESH
(P.601)
Open
SCR
detection trip threshold
45
ANLG
OUT
1
GAIN
ADJ
(P.420)
I/O Expansion kit analog output 1 gain adjust
gain * 1000
46
ANLG
OUT
2
GAIN
ADJ
(P.422)
I/O Expansion kit analog output 2 gain adjust
gain * 1000
47
Reserved
Tunable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.