Table 7.6 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Tunable Data (Drive Input Data)
Register
Bit
Parameter Name (Number)
Description
Settings
40
DIAMETER
REGISTER
(P.874)
Value assigned to
NORM
ROLL
DIAMETER
(P.131) when
DIAMETER
CALC
ENABLE
(P.826) =
DISABLE
.
1.000 to 2.000
41
ACCELERATION
TIME
(P.001)
Min. time to accelerate from zero to
GEAR
IN
SPEED
(P.011)
seconds * 10
42
DECELERATION
TIME
(P.002)
Min. time to decelerate from
GEAR
IN
SPEED
(P.011) to
zero
seconds * 10
43
MINIMUM
SPEED
(P.003)
Lowest operating speed
RPM
44
MAXIMUM
SPEED
(P.004)
Highest operating speed
RPM
45
POSITIVE
CURRENT
LIM
(P.005)
Highest amount of current for the forward bridge
46
NEGATIVE
CURRENT
LIM
(P.006)
Highest amount of current for reverse bridge
47
S
-
CURVE
ROUNDING
(P.014)
Amount of smoothing of speed/voltage loop reference
0 to 50%
48
TRIM
RANGE
(P.109)
Amount the trim reference will affect the drive reference
0.0 to 100.0%
49
SPD
LOOP
PI
PROP
GAIN
(P.211)
Speed loop
PI
proportional gain
0.10 to 128.00
50
SPD
LOOP
PI
LEAD
FREQ
(P.212)
Speed loop
PI
block lead break frequency
51
CML
PI
PROP
GAIN
(P.301)
CML
PI
proportional gain
52
CML
PI
LEAD
FREQUENCY
(P.302)
CML
PI
lead break frequency
0.000 to 4.000
53
TEN
PI
PROP
GAIN
(P.841)
Tension loop
PI
block proportional gain
0.001 to 32.767
54
TEN
PI
LEAD
FREQ
(P.840)
Tension loop
PI
block lead frequency
0.00 to 141.37 radians/second
55
TENSION
PI
LIMIT
(P.853)
Tension loop pi block high and low limits
0 to 4095
COUNTS
56
JOG
SPEED
(P.012)
Operating speed while jogging
0 to
BASE
SPEED
(P.017) in
FPM
57
STOP
MODE
SELECT
(P.114)
Selects how drive responds to a normal stop command
RAMP
;
COAST
/
DB
;
CURRENT
LIMIT
58
NETW
OUT
REG
1
SELECT
(P.902) Number of the parameter readable in Drop_1, register 7
If no valid parameter value selected, this is set to
0=motor speed in
RPM
59
NETW
OUT
REG
2
SELECT
(P.903) Number of the parameter readable in Drop_1, register 8
If no valid parameter value selected, this is set to
0=armature voltage in volts
60
NETW
OUT
REG
3
SELECT
(P.904) Number of the parameter readable in Drop_1, register 9
If no valid parameter value selected, this is set to
0=armature current in amps*10 or amps
Tunable data are read by the regulator approximately every 600 msec while Tune/Config Input Enable bit=1.