18
ANLG
TACH
VOLTS
/1000 (P.203)
Analog tach scaling from tach nameplate (V/1000
RPM
)
volts * 10
19
ARM
VOLTAGE
GAIN
ADJ
(P.204)
Scales the armature voltage signal
gain * 1000
20
ARM
VOLTAGE
ZERO
ADJ
(P.205)
Offset removed from armature voltage feedback
21
Reserved
22
PULSE
TACH
PPR
(P.207)
Pulses per revolution from the pulse encoder nameplate
23
PULSE
TACH
QUADRATURE
(P.208)
Enables or disables pulse encoder quadrature
0=
OFF
; 1=
ON
(quad decode)
24
CURRENT
COMPOUNDING
(P.209)
Sets the level of current compounding
%
25
SPD
LEADLAG
RATIO
(P.213)
Ratio between low and high break frequencies of speed
feedback lead/lag block
26
SPD
LEADLAG
LOW
FREQ
(P.214)
Low break frequency of speed feedback lead/lag block
radians/second * 100
27
SPD
LOOP
LAG
FREQ
(P.215)
Lag break frequency for speed loop forward path lag
radians/second * 100
28
SPD
LEADLAG
SELECT
(P.216)
Speed/voltage loop lead/lag block select
0=
LEAD
/
LAG
; 1=
BYPASS
; 2=
LAG
/
LEAD
29
SPD
LOOP
LAG
BYPASS
(P.217)
Speed/voltage loop lag block bypass
0=
OFF
(not bypassed); 1=
ON
(bypassed)
30
CML
FEEDBACK
GAIN
ADJ
(P.300)
Current minor loop feedback gain adjust
gain * 1000
31
ARMATURE
BRIDGE
POL
(P.394)
Active armature bridge
0=
OFF
(forward); 1=
ON
(reverse)
Table 6.14 – FlexPak 3000 Alternate Register Map, Drop_3: Master Write Registers, FULL Connection. Tunable Data (Drive Input Data)
Register
Bit
Parameter Name (Number)
Description
Settings
33
FIELD
ECONOMY
REF
(P.511)
Reference for field economy mode
% of
MOTOR
HOT
FLD
AMPS
(P.510)
34
FIELD
PI
PROP
GAIN
(P.514)
Proportional gain setting for the field current loop
PI
block gain * 100
35
FIELD
PI
LEAD
FREQ
(P.515)
Lead frequency for the field current loop
PI
block
radians/second * 100
36
FLD
FEEDBACK
GAIN
ADJ
(P.516)
Field current feedback gain adjust
gain * 1000
37
FLD
WEAKEN
THRESHOLD
(P.518)
Where field control loop begins regulating armature
voltage and the field begins to weaken
4095 at
MOTOR
RATED
ARM
VOLTS
(P.009)
38
FLD
WEAKEN
PROP
GAIN
(P.519)
Proportional gain of the field control loop’s armature
voltage regulator
gain * 100
39
FLD
WEAKEN
LEAD
FREQ
(P.520)
PI
block lead break frequency of the field control loop’s
armature voltage regulator
radians/second * 100
Tunable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1.
Table 6.13 – FlexPak 3000 Alternate Register Map, Drop_3: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
Register
Bit
Parameter Name (Number)
Description
Settings
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.