Table 5.2 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data)
Register
Bit
Parameter Name (Number)
Description
Settings
0
Drive status word 1
Bit-packed word containing information on the present status of the drive
0
Drive ready
1
Drive running
2
Fault active
3
Drive jogging
4
Forward/reverse command
0=forward; 1=reverse
5
Drive stopping
6
Tune/config input enable loopback
0=disabled; 1=enabled
7
Tune/config update synch. flag loopback (master read)
8
Alarm active
9
In current limit
10
Coast/DB interlock
0=open; 1=closed
11
Customer interlock
0=open; 1=closed
12
Parameter processing error
0=no errors; 1=one or more errors
13
Terminal strip forward/reverse input state (terminal 5)
14
Terminal strip auto/manual input state (terminal 6)
15
Terminal strip fault/alarm reset input state (terminal 10)
1
SPD
SOURCE
SELECT
OUT
(P.193)
Selected speed/voltage loop reference value
4095 at
TOP
SPEED
(P.011)
2
SPD
LOOP
REFERENCE
(P.295)
Final speed/voltage loop reference value
4095 at
TOP
SPEED
(P.011)
3
SPD
LOOP
FEEDBACK
(P.296)
Final speed/voltage loop feedback value after all scaling
4095 at
TOP
SPEED
(P.011)
4
SPD
LOOP
OUTPUT
(P.299)
Speed loop
PI
block output value
4095 at
MAXIMUM
CURRENT
(P.007
5
ARMATURE
VOLTAGE
(P.289)
Armature voltage feedback value
4095 at
MOTOR
RATED
ARM
VOLTS
(P.009)
6
Average
CML
feedback
CML
feedback average over eight
CML
scans
4095 at
MAXIMUM
CURRENT
(P.007)
7
Network Output Register 1
Value of the parameter selected by
NETW
OUT
REG
1
SELECT
(P.902)
If no valid parameter value selected,
0=motor speed in
RPM
8
Network Output Register 2
Value of the parameter selected by
NETW
OUT
REG
2
SELECT
(P.903)
If no valid parameter value selected,
0=armature voltage in volts
9
Network Output Register 3
Value of the parameter selected by
NETW
OUT
REG
3
SELECT
(P.904)
If no valid parameter value selected,
0=armature current in amps*10 or amps
10 to 15
Tunable, Configurable and Status Data
Runtime signal data are updated by the regulator every 5 msec, unless
FEEDBACK
SELECT
(P.200) is set to
ARMATURE
VOLT
, in which case the update time is 10 msec.