P.901 = use last ref (1), P.901 = use trmblk ref (2), P.901 = use trmblk cntl (3) – Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual
Page 22

3-4
AutoMax Network Communication Option Board
P.901 = USE LAST REF (1)
When
NETW
COMM
LOSS
SELECT
(P.901) is set to
USE
LAST
REF
and network
communication is lost, the following occurs:
•
The drive continues to run, using the last reference received from the network
master.
•
A
NETWORK
COMMUNICATION
TIMEOUT
alarm (A00004) is generated.
•
An entry is made into the drive’s alarm log for each active-to-inactive transition of
network communication status.
•
If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.
You can stop the drive using the hardwired stop input or the
OIM
STOP
/
RESET
key.
However, you cannot restart the drive until network communication is re-established or
CONTROL
SOURCE
SELECT
(P.000) is changed.
P.901 = USE TRMBLK REF (2)
When
NETW
COMM
LOSS
SELECT
(P.901) is set to
USE
TERMBLK
REF
(2) and network
communication is lost, the following occurs:
•
The drive continues to run, using the auto reference value selected by
AUTO
REFERENCE
SELECT
(P.103)
(or Regulator board terminals 19 and 20?)
•
A
NETWORK
COMMUNICATION
TIMEOUT
alarm (A000014) is generated.
•
If network communication is re-established and the drive is still running, the drive
will again follow the reference and sequencing control inputs supplied by the
network master.
You can stop the drive using the hardwired stop input, the
OIM
STOP
/
RESET
key, or the
hardwired stop input (coast/DB stop, Regulator board terminal 8). However, you
cannot restart the drive until network communication is re-established or
CONTROL
SOURCE
SELECT
(P.000) is changed.
P.901 = USE TRMBLK CNTL (3)
When
NETW
COMM
LOSS
SELECT
(P.901) is set to
USE
TRMBLK
CNTL
(3), and network
communication is lost, the following occurs:
•
The drive continues to run using the Regulator board terminal strip as the source for
all control (run, jog, stop, fault reset, direction, and OCL enable) and speed (auto)
reference signals.
•
A
NETWORK
COMMUNICATION
TIMEOUT
alarm (A000014) is generated.
•
The Speed Loop PI Reset and Underwind/Overwind bits cannot be changed while
operating in this mode. They will remain at the last values received from the
network.
If network communication is re-established and the drive is still running, the drive will
again frollow the reference and sequencing control inputs supplied by the network
master.