Table 5.3 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)
Register
Bit
Parameter Name (Number)
Description
Settings
10
Fault latch bits word 1
Bit-packed word indicating latched faults
0
AC
LINE
SYNCHRONIZATION
FAULT
(F00010)
1
FIELD
CURRENT
LOSS
(F00004)
2
SUSTAINED
OVERLOAD
(F00005)
3
SELF
TUNING
FAULT
(F00060 to F000099)
4
MOTOR
THERMOSTAT
TRIP
(F00008)
5
CONTROLLER
THERMOSTAT
TRIP
(F00009)
6
BLOWER
MOTOR
STARTER
OPEN
(F00006)
7
Reserved
8
IET
(
OVERCURRENT
) (F00001)
9
OVERSPEED
(F00003) /
ARMATURE
OVERVOLTAGE
(F00012)
10
SCR
N
or
MULTIPLE
SCRS
NOT
OPERATING
(F00030–F00042)
11
OPEN
ARMATURE
(F00007)
12
TACHOMETER
LOSS
(F00002)
13
OIM
COMMUNICATIONS
TIMEOUT
(F00011)
14
NETWORK
COMMUNICATION
TIMEOUT
(F00013)
15
REVERSED
TACH
LEADS
(F00014)
11
Reserved
12
First fault
Fault code of the first fault since the last fault reset
13
Alarm latch bits word
Bit-packed word containing latched alarm bits
0
MOTOR
BRUSH
WEAR
LOW
(A00001)
1
AC
LINE
VOLTAGE
LOW
(A00002)
2
AC
LINE
VOLTAGE
HIGH
(A00003)
3 to 15
Reserved
14
Last alarm
Alarm code of the most recent alarm
15
CONTROL
SOURCE
SELECT
(P.000)
Selected source for drive control signals
0=
TERMBLK
; 1=
KEYPAD
; 2=
SERIAL
; 3=
NETWORK
16
ACCELERATION
TIME
(P.001)
Min. time to accelerate from zero to
TOP
SPEED
(P.011)
seconds * 10
17
DECELERATION
TIME
(P.002)
Min. time to decelerate from
TOP
SPEED
(P.011) to zero
seconds * 10
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.