1 (con’t.), 10 to 15 – Rockwell Automation FlexPak/WebPak 3000 DC Drive AutoMax Network Communication Board User Manual
Page 54
6-
6
Aut
o
Max
Net
w
or
k Comm
unicat
ion
O
p
tion
B
oard
1 (con’t.)
13
Terminal strip auto/manual
14
Digital input 0
15
Motor thermostat
2
SPD
LOOP
REFERENCE
(P.295)
Final speed/voltage loop reference value
4095 at
TOP
SPEED
(P.011)
3
SPD
LOOP
FEEDBACK
(P.296)
Final speed/voltage loop feedback value after all scaling
4095 at
TOP
SPEED
(P.011)
4
SPD
LOOP
OUTPUT
(P.299)
Speed loop
PI
block output value
4095 at
MAXIMUM
CURRENT
(P.007)
5
ARMATURE
VOLTAGE
(P.289)
Armature voltage feedback value
4095 at
MOTOR
RATED
ARM
VOLTS
(P.009)
6
Average
CML
feedback
Current minor loop feedback average over 8
CML
scans
4095 at
MAXIMUM
CURRENT
(P.007)
7
Network Output Register 1
Value of the parameter selected by
NETW
OUT
REG
1
SELECT
(P.902)
If no valid parameter value selected,
0=motor speed in
RPM
8
Network Output Register 2
Value of the parameter selected by
NETW
OUT
REG
2
SELECT
(P.903)
If no valid parameter value selected,
0=armature voltage in volts
9
Network Output Register 3
Value of the parameter selected by
NETW
OUT
REG
3
SELECT
(P.904)
If no valid parameter value selected,
0=armature current in amps*10 or amps
10 to 15
Tunable, Configurable and Status Data
16
ANALOG
AUTO
REFERENCE
(P.188)
Analog reference value in auto mode after all scaling
4095 at
TOP
SPEED
(P.011)
17
ANALOG
MAN
TRIM
REF
(P.194)
Analog manual trim reference input value
4095 at
TOP
SPEED
(P.011)
18
ANLG
IN
1 (P.492)
I/O Exp. kit analog input 1 after gain and zero applied
4095 at full scale
19
ANLG
IN
2 (P.493)
I/O Exp. kit analog input 2 after gain and zero applied
4095 at full scale
20
FREQ
IN
(P.491)
I/O Expansion kit frequency input value after all scaling
4095 at full scale
21
OCL
OUTPUT
(P.848)
Outer control loop output value
RPM
22
FIELD
FEEDBACK
(P.589)
Motor field current feedback value after scaling and gain 4095 at
MOTOR
HOT
FLD
AMPS
(P.510)
23
AC
LINE
VOLTAGE
(P.392)
Measured AC line
RMS
voltage
volts
RMS
*
The I/O Expansion kit digital inputs do not have fixed functions when
CONTROL
SOURCE
SELECT
(P.000) is set to
NETWORK
. Therefore, they do not select preset speeds, change the
MOP
setpoint, or enable or disable the
OCL
.
Table 6.3 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
Register
Bit
Parameter Name (Number)
Description
Settings
Runtime signal data are updated by the regulator every 5 msec, unless
FEEDBACK
SELECT
(P.200) is set to
ARMATURE
VOLT
, in which case the update time is 10 msec.