Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Chapter 5 Create an RSLogix 5000 Software Project
3.
Review the checkboxes on this dialog box.
4.
Click OK.
Field
Description
Requested Packet Interval (RPI)
Choose the RPI to determine the rate at
which a communication module, such as a
1756-ENBT module, queries the block.
Inhibit Module
Check the box to prevent communication
between the owner-controller and the
module. This option allows for maintenance
of the module without faults being reported
to the controller.
See Module Inhibiting in the ControlLogix
Analog I/O Modules User Manual,
publication
information.
Major Fault On Controller If Connection Fails
While in Run Mode
Check the box to create a major fault if there
is a connection failure with the module while
in Run mode.
For important information on this checkbox,
see ‘Configure a Major Fault to Occur’ in the
Logix5000 Controllers Information and
Status Programming Manual,
publication
.
Use Unicast Connection on EtherNet/IP
Displays only for analog modules using
RSLogix 5000 software version 18 or later in
a remote EtherNet/IP chassis.
Use the default checkbox if there are no
other controllers in ’Listen’ mode and data is
to be sent to a specific owner-controller.
Clear the box if there are other ’listening’
controllers in the system.
Module Fault
If a fault occurs, its details appear in this
section of the tab.
IMPORTANT
Adding Logix Blocks online in RSLogix 5000 software with ‘Major
Fault on Controller If Connection Fails While in Run Mode’
checked may result in faulting the controller if the Logix Block has
not been already downloaded via RSFieldbus software or the
Logix Block is configured to use a scheduled connection.
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual