Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual
Page 39

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
39
Create an RSFieldbus Software Project Chapter 3
1.
Right-click the H1 icon and choose Configure Device Class.
The Device Class dialog box appears.
2.
Select the device that you want to change to a Backup LAS and click the
right arrow
.
3.
Repeat for any other devices that you want to change to a Backup LAS.
4.
Click Apply.
Change Device Class to Basic
Do these steps to change the device class of a device from Backup LAS to Basic.
1.
Right-click the H1 icon and choose Configure Device Class.
The Device Class dialog box appears.
ATTENTION: During this procedure, control of the associated devices
and anything linked to them will be lost.
This manual is related to the following products:
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual