Reset through rslogix 5000 software – Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual
Page 152

152
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Appendix A Troubleshoot the Linking Device
4.
Click End Edit.
The reset begins.
5.
Once Run appears in the value field, click Close.
6.
At the Save modified parameters dialog box, click No.
Reset through RSLogix 5000 Software
You can reset the linking device through RSLogix 5000 software without having
an RSFieldbus project configured or a Resource block downloaded. This reset
restarts the linking device and deletes all downloaded fieldb us configuration.
The linking device retains its network configuration and web page password
information through this reset.
Do these steps to perform a reset by using RSLogix 5000 software.
1.
Place your program in Program mode.
2.
On the I/O Configuration folder, right-click the linking device and choose
Properties.
The Module Properties dialog box appears.
3.
Click the Module Info tab and click Reset Module.
ATTENTION: You will lose the following linking device functions during
a reset:
•
Control of the current linking device process
•
Monitoring processes through the linking device
•
Communication to devices attached to the linking device
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual