Appendix A Troubleshoot the Linking Device
The table provides a description of the status indicators for channels on the
ControlNet network that are used along with the 1757-FFLDC linking device.
Alternating red/
green
Self-test
None.
Incorrect channel
configuration
Verify that the ControlNet network is connected to
the correct channel of the linking device (for
example), if the ControlNet network is configured for
channel A only, then the linking device must be
connected to the network via channel A).
Alternating red/off
Duplicate ControlNet
node address
• Choose a unique node address.
• Cycle power to the linking device.
Table 15 - ControlNet Channel Troubleshooting (A AND B)
AND Cause
Action
Off
Channel disabled.
Use RSNetwork for ControlNet software to
configure the ControlNet network for redundant
media, if required.
Solid green
Normal operation
None.
Flashing green/off
Temporary network
errors
• Check media for broken cables, loose connectors,
or missing terminators.
• If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication
.
Flashing red/off
Media fault
• Check media for broken cables, loose connectors,
or missing terminators.
• If condition persists, refer to the ControlNet
Media Planning and Installation Manual,
publication
.
No other nodes
present on network
Add other nodes to the network.
Flashing red/green
Incorrect ControlNet
node address
• Change linking device node address so that it is
less than or equal to UMAX.
(1)
• Cycle power to the linking device.
(1) UMAX is the highest node address on a ControlNet network than can transmit data.
Incorrect network
configuration
Use RSNetWorx for ControlNet software to
reconfigure the ControlNet network so that UMAX
is greater than or equal to the linking device’s
node address.
Table 14 - ControlNet Network Troubleshooting (A AND B)
AND Cause
Action
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual