Appendix D Connections
shows an example of counting your ControlNet network connections.
To determine the number of connections and packets per second for an Ethernet
network, use the EtherNet/IP Capacity tool at
.
In Example 1, if a 1756-CNB ControlNet bridge module is being used, the
network could be considered fully loaded because this module supports 64
connections.
In Example 2, if a 1756-CNB ControlNet bridge module is being used, the
network could be considered fully loaded and even too close to the connection
limit. We recommend that you have a number of spare connections for additional
connections that may occur.
Table 26 - ControlNet Network Examples
Example 1
Example 2
Number of 1757-FFLDC linking devices
3
10
Number of Logix Blocks used per
linking device
16
4
Class 1 connections
(1 per Logix Block)
48
40
Class 3 connections
(2 per linking device)
6
20
Controller connection to the ControlNet bridge or
interface module
1
1
Total connections
55
61
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual