Supported modes, Block_err, Parameters – Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual
Page 108: Supported modes block_err parameters
108
Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Chapter 7 Linking Device Function Blocks
Supported Modes
Out of Service (OOS) and AUTO are supported modes for the linking device.
BLOCK_ERR
The BLOCK_ERR of the resource block indicates the following causes for the
error:
•
Device Fault State Set – When FAULT_STATE is active.
•
Out of Service – When the block is in OOS mode.
Block Configuration Out of Service - Incorrect parameter value or uninitialized
value for a parameter that requires a value or selection for the block to operate.
Parameters
Table 5
describes the resource block parameters.
See
for Data Type and Structure definitions
.
Table 5 - RES Block Parameters
Index
Parameter
Data Type
(length)
Valid Range/
Options
Default
Value
Units
Edit
Mode
Description
1
ST_REV
Unsigned16
2 bytes
0
None
RO
The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
2
TAG_DESC
OctString(32)
4 bytes
Spaces
N/A
AUTO
The user description of the intended application of the
block.
3
STRATEGY
Unsigned16
2 bytes
0
None
AUTO
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
4
ALERT_KEY
Unsigned8
1 byte,
1 to 255
0
None
AUTO
The identification number of the plant unit. This
information may be used in the host for sorting alarms,
and so on.
5
MODE_BLK
DS-69
OOS
N/A
AUTO
See MODE Block Parameter in Chapter 2 of the
FOUNDATION Fieldbus Design Considerations
Reference Manual, publication
.
6
BLOCK_ERR
Bitstring(2)
E
RO
This parameter reflects the error status associated
with the hardware or software components associated
with a block. It is a bit string, so that multiple errors
may be shown.
7
RS_STATE
Unsigned8
E
RO
State of the function block application state machine.
8
TEST_RW
DS-85
None
AUTO
Read/write test parameter - used only for conformance
testing.
9
DD_RESOURCE
Visible String(32)
Spaces
N/A
RO
Not user configurable.
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual