Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
Chapter 5 Create an RSLogix 5000 Software Project
Add the Communication
Module, Linking Device,
and Logix Blocks
To communicate with the controller, you add a local communication module, the
linking device, and then the Logix Blocks. Within the I/O Configuration folder,
organize the modules into a hierarchy (tree/branch, parent/child).
Add the Communication Module
The communication bridge module establishes the EtherNet/IP address to allow
the linking device to communicate with the ControlLogix controller.
If configuring a 1757-FFLDC linking device, you add a ControlNet
communication module, such as a 1756-CNBR module.
Do these steps to create a communication module.
1.
Right-click the 1756 Backplane and choose New Module.
The Select Module dialog box appears with a list of module types.
2.
Click the ‘+’ sign in front of Communications.
A list of communication modules appears.
3.
Select the appropriate communication bridge module, such as the
1756-ENBT module.
4.
Click OK.
- 1757-FFLDC2 FOUNDATION Fieldbus System User Manual 1757-FFLD4 FOUNDATION Fieldbus System User Manual 1757-FFLD2 FOUNDATION Fieldbus System User Manual 9308-RSFB1024ENE FOUNDATION Fieldbus System User Manual 9308-RSFB256ENE FOUNDATION Fieldbus System User Manual 9308-RSFB64ENE FOUNDATION Fieldbus System User Manual