beautypg.com

Controlnet network status indicators – Rockwell Automation 1757-FFLDC4 FOUNDATION Fieldbus System User Manual User Manual

Page 147

background image

Rockwell Automation Publication 1757-UM012A-EN-P - July 2011

147

Troubleshoot the Linking Device Appendix A

ControlNet Network
Status Indicators

The table provides a description of the ControlNet network status indicators that
are used along with the 1757-FFLDC status indicators.

NS
(network status)

Off

Not powered.

Flashing green

No connections to the Logix Blocks in the controller
or to the Logix Blocks in the linking device.
Verify physical connection by using the

ControlNet status indicators.

Verify the following:

The Logix Block is downloaded to the controller

(via RSLogix 5000 software) and the linking
device (via RSFieldbus software).

The Logix Blocks’ slot numbers correspond in

RSLogix 5000 software and RSFieldbus
software.

The ControlNet network has been scheduled at

least once when using unscheduled
connections to Logix Blocks and all Logix
Blocks using scheduled connections have
been scheduled.

Solid green

CIP Class 1 connections.

Flashing red

Connection timeout.
Verify the linking device is connected to the
ControlNet network.

Solid red

Duplicate ControlNet node address.

Flashing red and
green

Self-test.

MODE

Solid green

Linking device is operational.

Flashing green

Linking device is out-of-service.
Verify that the Resource block is set to Target Auto
mode.

(1) If the BATT status indicator remains on after the jumper is replaced, and power has been returned to the linking

device, contact Rockwell Automation Technical Support.

Table 13 - 1757-FFLDC Status Indicators

Indicator

Status

Description

IMPORTANT

When you connect the module to a ControlNet network by using only the
network access port (NAP), the status indicators are not accurate.

Table 14 - ControlNet Network Troubleshooting (A AND B)

AND Cause

Action

Off

No power.

None or apply power to the linking device.

Faulted ControlNet
interface

Cycle power ti the linking device.
If fault persists, contact your Rockwell

Automation Technical Support representative or
distributor.

Invalid node address
of 00

Choose a valid node address.
Cycle power to the linking device.

Solid red

Faulted ControlNet
interface

Cycle power to the linking device.
If fault persists, contact your Rockwell

Automation Technical Support representative or
distributor.