Span Your Valves

Chapter 9

9-47

Set Profile Pressure Alarms

For clamp open profiles, set the maximum pressure alarm (FOC57,
SOC57, TOC57, OSC57) to a pressure value that should:

not be exceeded during the clamp profile
not exceed the max pressure control limit

FOC42, SOC42, TOC42, and OSC42

Entering a value of zero disables these alarms.

Download new values to the QDC module.

Important: If downloading from your programming terminal, download
FOC, SOC, TOC, OSC, and OPC in that order (chapter 4):

To download

Set B21/

FOC

16

SOC

17

TOC

18

OSC

19

OPC

20