Chapter 3 Wire Your Controller
Sinking and Sourcing
Wiring Diagrams
Any of the MicroLogix 1400 DC embedded input groups can be configured as
sinking or sourcing depending on how the DC COM is wired on the group.
1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA,
1766-L32AWAA, 1766-L32BXBA Wiring Diagrams
Figure 6 - 1766-L32AWA/L32AWAA Input Wiring Diagram
(1)
(1) “NOT USED” terminals are not intended for use as connection points.
Type
Definition
Sinking Input
The input energizes when high-level voltage is applied to the input terminal
(active high). Connect the power supply VDC (-) to the input group’s COM
terminal.
Sourcing Input
The input energizes when low-level voltage is applied to the input terminal
(active low). Connect the power supply VDC (+) to the input group’s COM
terminal.
ATTENTION: The 24V DC sensor power source must not be used
to power output circuits. It should only be used to power input
devices (for example. sensors, switches). See Master Control Relay
on page 13 for information on MCR wiring in output circuits.
TIP
In the following diagrams, lower case alphabetic subscripts are
appended to common-terminal connections to indicate that different
power sources may be used for different isolated groups, if desired.
NOT
USED
NOT
USED
COM 0
L2a
L1a
IN0
IN1
IN2
IN3
COM 1
L2b
L1b
IN4
IN5
IN6
IN7
COM 2
L2c
L1c
IN8
IN9
IN10
IN11
COM 3
L2d
L1d
IN12
IN13
IN14
IN15
IN17
IN18
IN19
IN16
COM
ANA
A
GND
A
IN0
IV0(+)
IV1(+)
IV2(+)
IV3(+)
A
IN1
A
IN2
A
IN3
1766-L32AWAA only