Rockwell Automation 1766-Lxxxx MicroLogix 1400 Programmable Controllers User Manual User Manual
Page 260

220
Rockwell Automation Publication 1766-UM001H-EN-P - May 2014
Appendix F MicroLogix 1400 Distributed Network Protocol (DNP3)
Expected Session Key Change Interval (x1 s) in Secure Authentication
This parameter is supported only in MicroLogix 1400 Series B controllers.
This parameter is used for configuring the expected session key change interval in
seconds.
The valid range is 0…7200 (2 hrs). Default value is 1800 (30 mins).
When DNP3 Master does not change the Session Key within this time
configured, the MicroLogix 1400 invalidate the Session Key and its state for each
user.
Expected Session Key Change Count in Secure Authentication
This parameter is supported only in MicroLogix 1400 Series B controllers.
This parameter is used for configuring the expected session key change count.
The valid range is 1 to 10000. Default value is 2000.
15 (0x0F)
N.A.
N.A.
16 (0x10)
critical
optional
17 (0x11)
critical
optional
18 (0x12)
critical
optional
19 (0x13)
N.A.
N.A.
20 (0x14)
critical
optional
21 (0x15)
critical
optional
22 (0x16)
-
-
23 (0x17)
-
optional
24 (0x18)
critical
optional
25 (0x19)
-
optional
26 (0x1A)
-
optional
27 (0x1B)
-
optional
28 (0x1C)
-
optional
29 (0x1D)
critical
optional
30 (0x1E)
-
optional
31 (0x1F)
critical
optional
32 (0x20)
N.A.
N.A.
33 (0x21)
N.A.
N.A.
129 (0x81)
-
optional
130 (0x82)
-
optional
131 (0x83)
N.A.
N.A.
Function Code
Critical FCs File Number = 0
Critical FCs File Number = 0